7-7

IM 21B04C50-01E

<Toc> <Ind>

<7. INTEGRATED VALVE INTERFACE (IVI)>

Table 7.1 IVI Faceplate Parameters

T0701.EPS

YVP output pressure for a Single Acting
actuator or output pressure of out1 for a
Double Acting actuator. Blue color.
Scale = TB.SUPPLY_PRESSURE

Device Operation State may be one of the following:
NORMAL (Automatic)
MANUAL
Out Of Service
If no physical device is selected, it displays
OFFLINE as the operation state.

This indicates the YVP’s tag.

Remarks

[PD.TAG]

[AO.OUT]

TB.FINAL_VALUE

TB.FINAL_POSITION_VALUE

TB.ELECT_TEMP

TB.OUT_PRESSURE

TB.SERVO_OUTPUT_SIGNAL

Parameter name

Display
parameter

Operational
State

Setpoint
Signal

Target
Position

Valve
Position

Temperature

Pressure

I/P

Block
modes

PD-Tag

Display
type

Active
control

Slider and
XX.XX%

Bar and
XX.XX%

Bar and XX
deg

Bar and
XX.XX Psi

Bar and
XX.XX%

Device environmental temperature
[-40, 85] Deg C or
[-40, 185] Deg F
Color: Yellow

Desired valve position before application of
characterization and limits

A right clicking on this display can change
the operation status.

Desired valve position as derived by the FF
input value into the YVP.

This indicates valve stem or shaft position in
percent of ranged travel.

Yellow: [0 to 20] %
Green: [20 to 80] %
Red:

[80 to 100] %

AUTO,CAS: Black
MAN:

Yellow

OOS:

Red

Color coded
Individual
boxes

Block.MODE BLK
Block = RB, TB, AO, DI, or PID

7.2.2

Block Actual Mode

The following table lists the supported modes of the valve positioner for each block.

Table 7.2 Block Modes

Block

Supported Modes

Resource

Auto, O/S

Transducer

Auto, O/S

AO

RCas, Cas, Auto, Man, (LO), (IMAN), O/S

DI

Auto, Man, O/S

OS

Cas, Auto, (IMan), O/S

PID

ROut, RCas, Cas, Auto, Man, (LO), (IMAN), O/S

7.2.3

Position

This frame displays the valve position setpoint with the slider and a bargraph.
The corresponding target position is displayed with a slider. The actual position is displayed
with a bargraph.

7.2.4

Other Status

It displays Analog Output (AO) and PID block schedule status, transducer (XD) Error
description, and communication error.