<17. FAILSAFE HANDLING>

IM 21B04C50-01E

WARNING

Setting the T2 Parameter, to cause failsafe after a sustained position error, can cause
unwanted process shutdowns. The T2 setting should be used cautiously. Care must be
taken to avoid interaction with other configuration parameters, particularly High and Low
Position limits.

Deviation Error, Air to close, High or low actuator pressure (Cases 2 and 4)

Table 17.2 Failsafe- Cases 2 and 4

T17.2eps

Case 2

Case 4

Valve fails closed with high actuator pressure.

After pressure problem is corrected, the valve is open in failsafe.
- As the problem is corrected the valve may move past setpoint and go to clear latch briefly.

XD Error: Deviation error appears in the Error status.
The Failsafe Status dialog appears and shows Active (Latched).

Failsafe type

Deviation Error

Actuator Action

Air to close
Fail Open

Cause of Failure

Valve fails open with low actuator pressure.

After the pressure problem is corrected, the valve remains open in failsafe.

XD Error: Deviation error appears in the Error status.
The Failsafe Status dialog appears and shows Active (Latched).

Failsafe type

Deviation Error

Actuator Action

Air to close
Fail Open

Cause of Failure

High actuator pressure

Observable
behavior

Supply pressure failure or low
actuator pressure

Observable
behavior

Figure 17.8

Failsafe Case 4 Steps 1 and 2