Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 11

Advertising
background image

<Toc> <Ind>

<1. Setup >

1-3

IM 77J04J11-01E 1st Edition : 2006.08.25-00

Address number (ADR)

Set the address number of the M Series itself. An address number of 1 to 99 can be as-
signed in any order. Note that the number of M Series that can be connected to a single
communication port is limited to 31.

Example of connecting four M Series to a higher-level device by setting address numbers
of 1, 5, 10 and 20

ADR=1

ADR=20

ADR=10

ADR=5

A maximum of 1200 m; up to 31 slave stations

PC

Baud rate (BPS)

Set the baud rate identical to that of the higher-level device to be connected. (Otherwise,
proper communication cannot be achieved.) The unit of the baud rate is kbps (kbits per
second).

Parity (PRI)

Set the handling of parity to be carried out when data is sent or received. Set the parity bit
state identical to that of the higher-level device to be connected.

Stop bit (STP)

Set the stop bit identical to that of the higher-level device to be connected.

Data length (DLN)

Set the data length identical to that of the higher-level device to be connected. (When
Ladder or MODBUS communication is selected in protocol selection, the data length is
fixed.)