Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 30

Advertising
background image

3-16

<Toc> <Ind>

<3. PC Link Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

WRW Writes data into D registers and I relays on a word-by-word basis in

random order

Function

Writes register data specified for each register into the registers specified in random order
by the specified number of words.

The number of words to be written into at a time is 1 to 32.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

1

2

2

1

3

2

5

1

4

1

Command

element

STX

Address

number

(ADR)

CPU

number

01

0

WRW

dddd1

Number

of words

(n)

Register

number 1

Comma

or space

Comma

or space

• • •

Checksum

dddd2

ETX

CR

• • •

4

Register

number 2

Comma

or space

5

1

ddddn

4

2

Register

number n

Comma

or space

5

1

1

1

Number of Bytes

1

2

2

2

2

1

1

Response

element

STX

Address

number

(ADR)

CPU

number

01

OK

CR

Checksum

ETX

Write data is specified in a 4-digit character string (0000 to FFFF) in hexadecimal.

Command (continued)

ddddn: write data of the specified number of words

ddddn is a character string in hexadecimal.

n=1 to 32

Example:

Writing 20.0 and 15.0 into the alarm-1 setpoint (D0101) and alarm-2 setpoint (D0102) of the M
Series with address number 10 respectively.

[Command]

[STX]10010WRW02D0101,00C8,D0102,00968F[ETX][CR]

200 in decimal
(Alarm-1 setpoint is 20.0.)

150 in decimal
(Alarm-2 setpoint is 150.0.)

OK is returned in response to the above command.

[Response]

[STX]1001OK5C[ETX][CR]

Advertising
This manual is related to the following products: