<Toc> <Ind>

<6. Functions and Usage of D Registers >

6-1

IM 77J04J11-01E 1st Edition : 2006.08.25-00

6.

Functions and Usage of D Registers

6.1

Overview of D Registers

This section describes the functions and usage of D registers.

The D registers store the input and output values, statuses and others that are
handled by the M Series. By connecting M Series to higher-level device capable of
PC link communication, Ladder communication or MODBUS communication, you
can readily use these internal data items by reading from or writing into the D regis-
ters.

6.2

Interpretation of D Register Map Table

This section explains how to read D Register Map tables in this chapter. The num-
bers listed in the leftmost column are D register numbers ((1) below). The five-digit
numbers in the next column are reference numbers used for MODBUS communica-
tion ((2) below). The numbers in the column third from left are register numbers in
hexadecimal used in MODBUS communication programs ((3) below).

D-Reg No.

Ref No.

H No.

Description

R/W

D0001

40001

0000

Status

R

D-Register Data Area

(1) D register number

(2) Reference number (for MODBUS communication)

Permission of read/write by communication

: Indicates that the number of writing
actions is limited to 100,000.

(3) Hex number (for MODBUS communication)

Advertising