Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 27

Advertising
background image

<Toc> <Ind>

<3. PC Link Communication >

3-13

IM 77J04J11-01E 1st Edition : 2006.08.25-00

WRD Reads D registers and I relays on a word-by-word basis

Function

Reads a sequence of contiguous register data on a word-by-word basis by the specified
number of words, starting at a specified register number.

The number of words to be read at a time is 1 to 64.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

• • •

1

2

2

2

4

4

4

2

1

1

CR

Response

element

STX

OK

dddd1

dddd2

ETX

Address

number

(ADR)

CPU

number

01

• • •

ddddn

Checksum

The response is returned in a 4-digit character string (0000 to FFFF) in hexadecimal.

ddddn: read data of the specified number of words

ddddn is a character string in hexadecimal.

n=1 to 64

Number of Bytes

1

2

2

1

3

5

1

2

2

1

1

Command

element

STX

Address

number

(ADR)

CPU

number

01

Register

number

Comma

or space

Number

of words

(n)

Checksum

0

WRD

ETX

CR

Example:

Reading the alarm-1 setpoint (D0101) of the M Series with address number 01.

[Command]

[STX]01010WRDD0101,0172[ETX][CR]

The alarm-1 setpoint 500 (01F4 [HEX]) is returned in response to the above command
(50.0 is expressed as 500).

[Response]

[STX]0101OK01F437[ETX][CR]

500 in decimal (Alarm-1 setpoint [A1] is 50.0.)