3 d register map table – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 62

Advertising
background image

6-2

<Toc> <Ind>

<6. Functions and Usage of D Registers >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

6.3

D Register Map Table

*1: User area applies when a graphic panel manufactured by Digital Corp. is used.

: The number of writing actions is limited to 100,000.

D-Reg No.

D0001

D0002

D0003

D0004

D0005 to D0100

D0101

D0102

D0103

D0104

D0105

D0106

D0107

D0108

D0109

D0110

D0111

D0112

D0113

D0114

D0115

D0116

D0117 to D0200

D0201

D0202

D0203

D0204

D0205

D0206 to D0209

D0210

D0211

D0212

D0213

D0214

D0215

D0216 to D0300

D0301

D0302

D0303

D0304

D0305

D0306

D0307 to D0308

D0309

D0310

D0311

D0312

D0313 to D0400

D0401 to D0450

Ref No.

40001

40002

40003

40004

40101

40102

40103

40104

40105

40106

40107

40108

40109

40110

40111

40112

40113

40114

40115

40116

40201

40202

40203

40204

40205

40210

40211

40212

40213

40214

40215

40301

40302

40303

40304

40305

40306

40309

40310

40311

40312

40401 to 40450

H No.

0000

0001

0002

0003

0064

0065

0066

0067

0068

0069

006A

006B

006C

006D

006E

006F

0070

0071

0072

0073

00C8

00C9

00CA

00CB

00CC

00D1

00D2

00D3

00D4

00D5

00D6

012C

012D

012E

012F

0130

0131

0134

0135

0136

0137

0190 to 01C1

R/W

R

R

R

R

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R/W

R

R

R

R

R/W

Description

Status

Alarm status

Input value (display value)

Input unit

Alarm-1 setpoint (A1)

Alarm-2 setpoint (A2)

Alarm-3 setpoint (A3)

Alarm-4 setpoint (A4)

Alarm-1 action (AL1)

Alarm-2 action (AL2)

Alarm-3 action (AL3)

Alarm-4 action (AL4)

Alarm-1 hysteresis (HY1)

Alarm-2 hysteresis (HY2)

Alarm-3 hysteresis (HY3)

Alarm-4 hysteresis (HY4)

Alarm ON delay (OND)

Alarm OFF delay (OFD)

Setpoint (SP)

Keylock (LOC)

Bias (BS)

Economical mode (ECO)

Burnout action (BSL)

Wiring resistance correction (WIR)

RJC sensor (RJC)

Communication protocol (PSL)

Address number (ADR)

Baud rate (BPS)

Parity (PRI)

Stop bit (STP)

Data length (DLN)

Range code number (IN)

Maximum measured input value (RH)

Minimum measrued input value (RL)

Decimal point position of scaling value (SDP)

Maximum scaling value (SH)

Minimum scaling value (SL)

Input adjustment point LOW (BL)

Input adjustment LOW (AL)

Input adjustment point HIGH (BH)

Input adjustment HIGH (AH)

User area *1

D-Register Data Area