2 response error codes, Message format in the event of error, Response error codes – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 58

Advertising
background image

5-12

<Toc> <Ind>

<5. MODBUS Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

5.2.2

Response Error Codes

Message Format in the Event of Error

If there are any inconsistencies other than communication errors in a message, the M
Series does nothing, but returns the following message.

Number of bytes in RTU mode

Number of bytes in ASCII mode

2

2

Address

Number

(ADR)

Element

Function Code

(*1)

Error Code

Error Check

[CR] [LF]

2

None

2

1

2

1

2

1

*1: In this case, a value of [function code (hexadecimal number) + number 80 (hexadecimal number)] is set.

Response Error Codes

Table 5-3

List of Error Codes

01

Error Code

Meaning

Cause

02

D-register number error

Function code error

03

D-register count error

Specified D register number is out of the range.

No such function code exists.

Specified number of D registers is out of the range.

Even when a message is sent, no response returns if:

Retransmission error (overrun, framing, parity, LRC, or CRC-16 error) was detected.

Address in a command message is incorrect.

Interval between data composing a message was 2 seconds or more.

CRC-16 or LRC values are incorrect.

Broadcase is specified (address number: 00).

Note: As a countermeasure, provide a timeout process in the communication functions of a higher-level device or in the

communication program.