Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 22

Advertising
background image

3-8

<Toc> <Ind>

<3. PC Link Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

BWR Writes data into I relays on a bit-by-bit basis

Function

Writes ON/OFF data into a sequence of contiguous I relays by the specified number of bits,
starting at a specified I relay number.

The number of bits to be written into at a time is 1 to 256.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Command

element

STX

Address

number

(ADR)

CPU

number

01

0

BWR

d1

d2

I relay

number

Comma

or space

Number

of bits

(n)

Comma

or space

• • •

dn

Checksum

ETX

Write data 0 and 1 indicate OFF and ON respectively.

Command (continued)

• • •

1

2

1

CR

1

OK

ETX

CR

Response

element

STX

Address

number

(ADR)

CPU

number

01

Checksum

Number of Bytes

1

2

2

2

2

1

1

Number of Bytes

1

2

2

1

3

5

1

3

2

1

1

dn: write data of the specified number of bits (n=1 to 256)

dn=0 (OFF)

dn=1 (ON)

Example:

Setting the user-defined flag of the M Series with address number 01 to ON.

The following command writes ON into the user-defined flag (I0033) of address number 01.

[Command]

[STX]01010BWRI0033,001,106[ETX][CR]

Note: The user-defined flags are flags that the user can freely read/write.

OK is returned in response to the above command.

[Response]

[STX]0101OK5C[ETX][CR]