Example:

Setting 70.00 into the alarms-1 setpoint of the M Series with address number 01.

The following message writes 70.00 into the alarms-1 setpoint (D0101) of address number
01 in the ASCII mode.

[Message]

Start of message mark

: 010600641B5822[CR][LF]

"01": address number 01, "06": function code 06, "0064": D-register number 0101,

"1B58": data 70.00, and "22": error check

Note: The numbers in quotation marks are hexadecimal.

The following response is returned with respect to the above message.

[Response]

: 010600641B5822[CR][LF]

Alarm-1 setpoint is 70.00.