Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 31

Advertising
background image

<Toc> <Ind>

<3. PC Link Communication >

3-17

IM 77J04J11-01E 1st Edition : 2006.08.25-00

WRS Specifies D registers and I relays to be monitored on a word-by-word

basis

Function

Specifies the register numbers to be monitored on a word-by-word basis. Note that this
command simply specifies the registers. Actual monitoring is performed by the WRM
command after the register numbers are specified by this command.

When the volume of data is large and you wish to increase the baud rate, it is effective to
use a combination of the WRS and WRM commands rather than just the WRR command.

If the power supply is turned off, the specified register numbers will be erased.

The number of words to be specified at a time is 1 to 32.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

1

2

2

1

3

2

5

1

5

1

CPU

number

01

Command (continued)

5

2

1

1

• • •

Command

element

STX

Address

number

(ADR)

Number

of words

(n)

Register

number 1

Comma

or space

Register

number 2

Comma

or space

0

WRS

Register

number n

ETX

CR

• • •

Checksum

1

2

2

2

2

1

1

Number of Bytes

ETX

CR

Response

element

STX

Address

number

(ADR)

CPU

number

01

OK

Checksum

Example:

Specifying that the alarm-1 setpoint and alarm-2 setpoint of the M Series with address
number 01 are to be monitored

(This command simply specifies the registers to be monitored.)

[Command]

[STX]01010WRS02D0101,D010289[ETX][CR]

CPU number: 01

D register numbers

OK is returned in response to the above command.

[Response]

[STX]0101OK5C[ETX][CR]