<5. MODBUS Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

Example:

Reading the statuses of alarm-1 and alarm-2 setpoints of the M Series with address num-
ber 01.

The following message reads two successive D registers starting at alarm-1 setpoint
(D0101) of address number 01 in the ASCII mode.

[Message]

Start of message mark

: 01030064000296[CR][LF]

"01": address number 01, "03": function code 03, "0064": D-register start number 0101,

"0002": number of D registers 2, and "96": error check

Note: The numbers in quotation marks are hexadecimal.

The following response is returned with respect to the above message.

[Response]

: 01030400010000F7[CR][LF]

Alarm-1 setpoint is 1.

Alarm-2 setpoint is 0.