Brm monitors i relays on a bit-by-bit basis, Function, Command/response (for normal operation) – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 26: Example

Advertising
background image

3-12

<Toc> <Ind>

<3. PC Link Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

BRM Monitors I relays on a bit-by-bit basis

Function

Reads the ON/OFF statuses of the I relays that have been specified in advance by the
BRS command.

Before executing this command, the BRS command must always be executed to
specify which I relays are to be monitored. If no relay has been specified, error code
06 is returned.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

1

2

2

1

3

2

1

1

Command

element

STX

0

BRM

ETX

CR

Address

number

(ADR)

CPU

number

01

Checksum

• • •

Number of Bytes

1

2

2

2

1

1

1

1

2

1

1

Response

element

STX

OK

d1

d2

d3

ETX

CR

Address

number

(ADR)

CPU

number

01

• • •

dn

Checksum

Responses 0 and 1 indicate OFF and ON respectively.

dn: read data of the number of bits specified by the BRS command (n=1 to 32)

dn=0 (OFF)

dn=1 (ON)

Example:

Monitoring the burnout, alarm 1 and alarm 2 of the M Series with address number 01 when
they have been specified to be monitored.

(This command reads the statuses of the I relays specified by the BRS command.)

[Command]

[STX]01010BRMA3[ETX][CR]

The ON/OFF statuses of the I relays are returned with respect to the above command.

[Response]

[STX]0101OK000EC[ETX][CR]

All have been OFF.

Advertising