1.

Setup

This chapter describes the setup procedure required to use the communication
functions (PC link, Ladder and MODBUS) and the communication parameters of the
M Series.

1.1

Setup Procedure

Set up the communication functions on the M Series as follows:

Set up the communication function parameters of the M Series. (See section 1.2.)

Connect a higher-level device and a M Series. (See the connection diagram below.)

Create communication programs for the higher-level device to perform communication.

Note: Refer to the documentation of each higher-level device when creating communication programs.

B (+)

A (-)

Shielded

B (+)

A (-)

B (+)

A (-)

M Series

M Series

PLC

JIS Class D grounding
(grounding resistance of 100

or less)

JIS Class D grounding
(grounding resistance of 100

or less)

Terminating resistor

220

1/4 W

Terminating resistor

220

1/4 W

• Connection

1

2

3

1

2

3

SG

COM

COM

B (+)

A (-)

B (+)

A (-)

B (+)

A (-)

M Series

M Series

PC or PLC

JIS Class D grounding
(grounding resistance
of 100

or less)

Terminating resistor

220

1/4 W

JIS Class D grounding
(grounding resistance
of 100

or less)

1

2

3

1

2

3

COM

COM

ML2

(RS-232C/RS-485 converter)

RS-232C

(straight cable)

4

3

5

SG

Advertising