<5. MODBUS Communication >

IM 77J04J11-01E 1st Edition : 2006.08.25-00

5.2

Function Codes

5.2.1

List of Function Codes

Function codes are command words used by the higher-level device to obtain the D regis-
ter data of the M Series.

Table 5-2

List of Function Codes

Code Number

03

Reads data from multiple
registers.

Capable of reading data from a maximum of 64 successive
registers.

06

Writes data into a register.

Capable of writing data into one register.

Writes data into multiple
registers.

16

Capable of writing data into a maximum of 64 successive
registers.

Performs loop back test.

08

Used to check the connection for communication.

Function

Description

The write function codes will not write into read-only or disabled registers.

Broadcast addressing is possible with function codes 06 and 16 only. (Also in this
case, read-only or disabled registers will not be written into.)