Function, Command/response (for normal operation), Example – Yokogawa JUXTA M Series Digital Limit Alarms MVTK User Manual

Page 23

Advertising
background image

<Toc> <Ind>

<3. PC Link Communication >

3-9

IM 77J04J11-01E 1st Edition : 2006.08.25-00

BRR Reads I relays on a bit-by-bit basis in random order

Function

Reads the ON/OFF statuses of the individuaI I relays specified in random order by the
specified number of bits.

The number of bits to be read at a time is 1 to 32.

For the format of response in the event of failure, see subsection 3.1.2.

The command shown below includes the checksum function.
When performing communication without checksum, do not include the 2-byte
checksum element in the command.

Command/Response (for normal operation)

Number of Bytes

1

2

2

1

3

2

5

1

5

1

Command

element

STX

Address

number

(ADR)

CPU

number

01

0

BRR

Number

of bits

(n)

I relay

number 1

Comma

or space

I relay

number 2

Comma

or space

• • •

I relay

number n

Checksum

ETX

CR

• • •

5

2

1

1

Number of Bytes

• • •

1

1

2

2

2

1

1

2

1

1

Response

element

STX

Address

number

(ADR)

CPU

number

01

OK

d1

d2

CR

• • •

dn

Checksum

ETX

Responses 0 and 1 indicate OFF and ON respectively.

Command (continued)

dn: read data of the specified number of bits (n=1 to 32)

dn=0(OFF)

dn=1(ON)

Example:

Reading the statuses of alarms 1 and alarm 2 of the M Series with address number 01.

The following command reads the statuses of alarm 1 (I0001) and alarm 2 (I0002) of
address number 01.

[Command]

[STX]01010BRR02I0001,I00027B[ETX][CR]

The ON and OFF responses are returned for alarm1 and alarm 2 respectively with respect
to the above command.

[Response]

[STX]0101OK10BD[ETX][CR]

Alarm 1 has been ON.