Star Water Systems SJ10 User Manual

Page 6

Advertising
background image

6

95 North Oak Street • Kendallville, IN 46755 • © 2014 Star Water Systems. All rights reserved.

pipe And Fittings

3. Use galvanized steel or NSF Pw Schedule

40 PVC pipe and fittings. This material is

designed for water pressure and will seal

against air and water under pressure. Do

not use DWV fittings, as these are designed

for drains without pressure and will not seal

properly.

CAUTiON: The entire system must be

air and water tight for efficient operation and to

maintain prime.

Wire Size:

The wire size is determined by the distance from

the power source to the pump motor and the

horsepower rating of the motor. See Table a for

proper wire size.

1 in. NPT

Discharge

1-1/4 in.

Suction

1 in.

Pressure

Pipe

3

Ventilation - Ventilation and drainage must be provided to prevent damage to the motor from heat

and moisture.

Freezing - Pump and all piping must be protected from freezing. If freezing weather is forecast, drain

pump or remove completely from the system.

Water Supply - The water source must be able to supply enough water to satisfy the capacity of

pump and water needs. See performance chart on page 2.

Suction lift - Suction lift is the vertical distance from the lowest level of the water to the pump intake.

See performance chart on page 2.

Horizontal Distance - The horizontal distance is the horizontal measurement between pump suction

and the water source. This distance may affect the ability of pump to operate. If it is more than 100 ft.,

call the manufacturer for assistance 1-800-742-5044.

GeNeRAl pUMp iNFORMATiON

wire Size Chart - Table a

Recommended Copper wire and Fuse Sizes

HP Rating of Single Phase Motors

Distance from

Motor to Meter 1/2

3/4

1

0-50’

115 V

230 V

14 Ga

14 Ga

14 Ga

14 Ga

12 Ga

14 Ga

50-100’

115 V

230 V

12 Ga

14 Ga

12 Ga

14 Ga

12 Ga

14 Ga

100-150’

115 V

230 V

12 Ga

14 Ga

10 Ga

12 Ga

10 Ga

12 Ga

150-200’

115 V

230 V

12 Ga

14 Ga

10 Ga

12 Ga

8 Ga

12 Ga

200-300’

115 V

230 V

10 Ga

14 Ga

8 Ga

10 Ga

6 Ga

10 Ga

Fuse Size

115 V

230 V

amps

15

15

amps

15

15

amps

20

15