400 series, En - 15, The previous anomalous results cannot be saved – HT instruments SPEED418 User Manual

Page 16

Advertising
background image

400

Series

EN - 15

4.

The results displayed can be saved by pressing the SAVE key twice or the
SAVE

key and, subsequently, the ENTER key (§ 9.1)

5. If the instrument detects that

the phase and neutral leads
are inverted, the message
reported here to the side is
displayed. Rotate the shuko
plug or check the connection
of the single cables

A U T O

R a = - - - -

T r c d = - - - - m s

R P - P e = - - - - M

REVERSE P-N

The phase and neutral conductors
are inverted

30mA

50V 500V

IdN

RCD UL VNom

6. If the instrument detects that

the phase and earth leads
are inverted, the message
reported here to the side is
displayed. check the
connection of the cables

A U T O

R a = - - - -

T r c d = - - - - m s

R P - P e = - - - - M

REVERSE P-PE

The phase and earth conductors are
inverted

30mA

50V 500V

IdN

RCD UL VNom

7. If the instrument detects a

phase-to-neutral voltage and
a phase-to-earth voltage
lower than the limit, the
message reported here to
the side is displayed. Check
that the system being tested
is energized

A U T O

R a = - - - -

T r c d = - - - - m s

R P - P e = - - - - M

Low voltage

Insufficient voltage

30mA

50V 500V

IdN

RCD UL VNom

8. If the instrument detects a

phase-to-neutral voltage or a
phase-to-earth voltage higher
than the limit, the message
reported here to the side is
displayed. Check that the
instrument is not phase-to-
phase connected

A U T O

R a = - - - -

T r c d = - - - - m s

R P - P e = - - - - M

High voltage

High voltage detected

30mA

50V 500V

IdN

RCD UL VNom

9.

The previous anomalous results cannot be saved