HT instruments SPEED418 User Manual

Page 69

Advertising
background image

400

Series

EN - 68

12.2. SAFETY SPECIFICATION
12.2.1. General
Instrument safety:

IEC/EN61010-1, IEC / EN61557-1, -2, -3, -4, -6, -7

Technical documentations:

IEC/EN61187

Accessory safety:

IEC/EN61010-031, IEC/EN61010-2-032

Insulation:

double insulation

Pollution level:

2

Max height of use:

2000m (6562ft)

Overvoltage category:

CAT III 240V to earth, max 415V among inputs P, N, PE

5V to ground, max 7.2V

peak to peak

between pins of In1 Input

12.2.2. Reference standards for verification measurements
LOW

 (200mA):

IEC/EN61557-4

M

: IEC/EN61557-2

RCD: IEC/EN61557-6
LOOP P-P, P-N, P-PE:

IEC/EN61557-3

Ra 15

mA

IEC/EN61557-3

123: IEC61557-7

12.2.3. AUX
Sound level measurement:

IEC/EN60651:1994/A1 type 1, IEC/EN60804:1994/A2 type 1

12.3. GENERAL CHARACTERISTICS
Mechanical data
Dimensions (L x W x H):

235 x 165 x 75mm (9 x 6 x 3in)

Weight (batteries included): 1250g (44ounces)

Power supply
Battery type:

6 batteries 1.5 V – LR6 – AA – AM3 – MN 1500

Low battery indication:

the symbol

is displayed when the battery voltage

is too low

Battery life:

approx >600 tests in all safety tests

approx 48 hours in PWR function

Auto power off:

if set to ON after about 5 minutes from the last key press or
measurement the instrument turns off automatically

Miscellaneous
Display:

LCD custom with backlight 73x65 mm

Memory:

500 memory locations

PC interface:

optical port

12.4. ENVIRONMENT
12.4.1. Environmental working conditions
Reference temperature:

23° ± 5°C (73°F ± 41°F)

Working temperature:

0 ÷ 40°C (32°F ÷ 104°F)

Relative humidity allowed:

<80%HR

Storage temperature:

-10 ÷ 60°C (14°F ÷ 140°F)

Storage humidity:

<80%HR

This instrument satisfies the requirements of Low Voltage Directive 2006/95/EC

(LVD) and of EMC Directive 2004/108/EC

12.5. ACCESSORIES
See packing list.