Measurement of the active, reactive and apparent power @ Vmis>60V, cos

=1, f=50.0Hz

Range [W, VAR, VA]

Resolution [W, VAR, VA]

Clamp full scale

[A]

Uncertainty

0.0

 999.9

0.1

FS ≤ 1

(1.0rdg + 6dgt)

1.000

 9.999 k

0.001 k

0.000

 9.999 k

0.001 k

1 < FS ≤ 10

10.00

 99.99 k

0.01 k

0.00

 99.99 k

0.01 k

10 < FS ≤ 100

100.0

 999.9 k

0.1 k

0.0

 999.9 k

0.1 k

100 < FS ≤ 3000

1000

 9999 k

1 k

Measurement of the power factor (cos

) @ Vmis>60V, f=50.0Hz

Current range [A]

Range

Resolution

Uncertainty

0.005

 0.1 x FS

0.80c

 1.00  0.80i

0.01

 2°

0.1

 1.2 x FS

 1°