400 series, En - 46 – HT instruments SPEED418 User Manual

Page 47

Advertising
background image

400

Series

EN - 46

5. If the instrument detects that

the phase and earth leads
are inverted, the message
reported here to the side is
displayed. Check the
connection of the cables

R a

----

- - - A

FRQ=50.0Hz
VP-N= 1V

VP-Pe=231V

REVERSE P-PE

The phase and earth conductors are
inverted

50V

UL

6. If the instrument detects a

phase-to-neutral voltage and
a phase-to-earth voltage
lower than the limit, the
message reported here to
the side is displayed. Check
that the system being tested
is energized

R a

----

- - - A

FRQ=50.0Hz
VP-N= 1V

VP-Pe= 1V

Low voltage

Insufficient voltage

50V

UL

7. If the instrument detects a

phase-to-neutral voltage or a
phase-to-earth voltage higher
than the limit, the message
reported here to the side is
displayed. Check that the
instrument is not phase-to-
phase connected

R a

----

- - - A

FRQ=50.0Hz
VP-N=281V

VP-Pe=280V

High voltage

High voltage detected

50V

UL

8. If the instrument detects a

phase-to-neutral voltage
lower than the minimum limit,
it does not perform the test and
displays the message
reported here to the side.
Check the efficiency of the
neutral conductor

R a

----

- - - A

FRQ=50.0Hz
VP-N= 1V

VP-Pe=231V

MISSING N

Missing neutral conductor

50V

UL

Advertising