999ms, Caution, 400 series – HT instruments SPEED418 User Manual

Page 29: En - 28, X½ mode as an alternative

Advertising
background image

400

Series

EN - 28

7. Once test is completed, in

case all six tests have had a
positive result, the
instrument displays a screen
similar to the one reported
here to the side

R C D

180°

x 1 / 2 > 9 9 9 m s > 9 9 9 m s
x 1 2 8 m s

3 1 m s

x 5 8 m s

1 0 m s

FRQ=50.0Hz

Ut=1.4V

VP-N=228V

VP-Pe=228V

Tripping times (expressed in ms)

RCD OK

AUTO 30mA

50V

Func

IdN RCD UL

8.

The results displayed can be saved by pressing the SAVE key twice or the
SAVE

key and, subsequently, the ENTER key (§ 9.1)


6.4.2. x½

mode

As an alternative:

5.

Press the GO/STOP key on the instrument or the START key on
the remote probe once. The instrument will start measuring with
a “0°” type current, injecting a current in phase with the positive
half-wave of voltage.

Or:

5.

Press the GO/STOP key on the instrument twice or the START key
on the remote probe before the hyphens disappear. The instrument
will start measuring with a “180°” type current, injecting a current in
phase with the negative half-wave of voltage.

CAUTION

If message “Measuring…” appears on the display, the instrument is
performing measurement. During this whole stage, do not disconnect the
test leads of the instrument from the mains.

6. If the RCD does not trip, the

instrument gives a double
acoustic signal which signals
the positive result of the test
and then displays a screen
similar to the one reported
here to the side

R C D

> 999ms

FRQ=50.0Hz

Ut=1.4V

VP-N=228V

VP-Pe=228V

0° or 180° type current

Tripping time of the RCD

Detected value for contact voltage Ut
compared to the nominal value of
the set residual current

RCD OK

x1/2 30mA

50V

Func

IdN RCD UL

7.

The results displayed can be saved by pressing the SAVE key twice or the
SAVE

key and, subsequently, the ENTER key (§ 9.1)