Specifications – HT instruments SPEED418 User Manual

Page 65

Advertising
background image

400

Series

EN - 64

12. SPECIFICATIONS

12.1. TECHNICAL FERATURES

Continuity test (LOW

)

Range [

] Resolution

[

]

Uncertainty

0.00

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 99.9

0.1

Test current >200mA DC up to 5

 (include the resistance of the calibration) also with half-charged battery

Generated current

resolution 1mA,

uncertainty

(5.0%rdg + 5dgt)

Open circuit test voltage

4 < V

0

< 24V

Function mode:

AUTO: automatic inversion of polarity, buzzer ON fixed if test current < 200mA

R+, R-: fixed polarity (opposite to R+ ed R-), buzzer ON fixed if test current < 200mA

Insulation resistance (M

)

Test voltage [V]

Range [

] Resolution

[

]

Uncertainty

50

0.01

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 49.9

0.1

50.0

 99.9

0.1

(5.0rdg + 2dgt)

100

0.01

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 99.9

0.1

100

 199

1

(5.0rdg + 2dgt)

250

0.01

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 99.9

0.1

100

 249

1

250

 499

1

(5.0rdg + 2dgt)

500

0.01

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 99.9

0.1

100

 499

1

500

 999

1

(5.0rdg + 2dgt)

1000

0.01

 9.99

0.01

(2.0rdg + 2dgt)

10.0

 99.9

0.1

100

 999

1

1000

 1999

1

(5.0rdg + 2dgt)

Open circuit test voltage

< 1.25 x nominal test voltage

Short circuit current

< 15mA (peak) with each test voltage

Generated voltage

resolution: 1V, uncertainty

(5.0%rdg + 5dgt) @ Rmis> 0.5% FS

Nominal test current

> 2.2mA with 230k

 @ 500V

> 1mA with 1k

 @ other Vnom

Test on RCDs

Phase-neutral and phase-earth voltage range

(110

 240V) 10%

Frequency 50Hz

0.5Hz, 60Hz 0.5Hz

Nominal test current (IdN)

10mA, 30mA, 100mA, 300mA, 500mA, 650mA

Contact voltage (ULIM)

25V, 50V

Tripping time (x½, x1, x2, x5, AUTO)

Multiplier [x IdN]

Range [ms]

Resolution [ms]

Uncertainty

½, 1

1

 999 general and selective

1

(2.0rdg + 2dgt)

2

1

 200 general

1

 250 selective

5

1

 50

general

1

 160 selective

RCD type

AC (

), A (

), general and selective

Nominal test current (IdN) multiplier x1, x2, x5, AUTO:

uncertainty: -0%, +10% IdN

multiplier x½:

uncertainty: -10%, +0% IdN

Advertising