400

Series

EN - 65

Tripping current ( )

IdN [mA]

Type

Range IdN [mA]

Resolution [mA]

Uncertainty

≤ 10

AC

(0.5

 1.1) IdN

0.1IdN -0%,

+10%rdg

A

(0.3

 1.1) IdN

> 10

AC

(0.5

 1.1) IdN

A

(0.3

 1.1) IdN

RCD type

AC (

), A (

), general and selective

Tripping time

resolution 1ms,

uncertainty

(2.0%rdg + 2dgt)

Earth resistance (Ra)

Range [

] Resolution

[

]

Uncertainty

1

 1999

1

(5.0rdg + 3dgt)

RCD type

AC (

), A (

), general and selective

Test current

< ½ IdN,

uncertainty: -10%, +0% IdN

Contact voltage Ut

range: 0

 2Ut lim

resolution: 0.1V

uncertainty: -0%, +(5%rdg + 3dgt)

Line impedance and fault loop impedance (LOOP)

Phase-neutral and phase-earth voltage range

(110

 240V) 10%

Phase-phase voltage range

(110

 415V) 10%

Frequency 50Hz

0.5Hz, 60Hz 0.5Hz

TT and TN systems

Range [

] Resolution

[

]

Uncertainty

0.01

 9.99

0.01

(5.0rdg + 3dgt)

10.0

 199.9

0.1

200

 1999 (phase-earth only)

1

Max peak test current at test voltage

3A @ 127V, 6A @ 230V, 10A @ 400V

IT systems

Range [mA]

Resolution [mA]

Uncertainty

5

 999

1

(5.0rdg + 3dgt)

Contact voltage (ULIM)

25V, 50V

Total earth resistance (Ra)

Range [

] Resolution

[

]

Uncertainty

0.01

 9.99

0.01

(5.0rdg + 1)

10.0

 199.9

0.1

200

 1999 (phase-earth only)

1

Test current

<15mA

Contact voltage (ULIM)

25V, 50V

Phase-neutral and phase-earth voltage range

(110

 240V) 10%

Frequency 50Hz

0.5Hz, 60Hz 0.5Hz

Phas sequence (123)

Phase-neutral and phase-earth voltage range

(110

 240V) 10%

Frequency 50Hz

0.5Hz, 60Hz 0.5Hz

Leakage current (LEAK)

Range [mV]

Resolution [mV]

Uncertainty

1

 1200.0

0.1

(1.0rdg + 2dgt)

Max crest factor

 3

Response time

10ms

Frequency 50Hz

0.5Hz, 60Hz 0.5Hz

Advertising