Caution, 400 series, En - 37 – HT instruments SPEED418 User Manual

Page 38

Advertising
background image

400

Series

EN - 37

RMT

The virtual RMT key, active only when the Z2Ω mode has been
selected with the MOD key, displays the serial number and the FW
version of the remote unit IMP57

3. If possible, disconnect all loads connected downstream of the measured point, as the

impedance of these users could distort the test results.

4. Use the virtual Mod. key to set the STD test mode.

Should you perform high-resolution tests, recommended
near MT/BT transformers, we suggest using the Z2

mode, which implies the use of the optional accessory
IMP57. Upon the selection of the Z2

 mode, the

instrument displays a screen similar to the one reported
here to the side. Connect accessory IMP57 to the
instrument by means of the serial optical cable and
perform the measurements as described in the relevant
user manual.

L O O P

----

- - - - A

FRQ=50.0Hz
VP-N=228V

VP-Pe=228V

P-N

Z2

Func

Mod.

5. Insert the green, blue and black connectors of the three-pin shuko cable into the

corresponding input leads E, N and P of the instrument. As an alternative, use the
single cables and apply the relevant alligator clips to the free ends of the cables. It is
also possible to use the remote probe by inserting its multipolar connector into the
input lead P. Connect the shuko plug, the alligator clips or the remote probe to the
electrical mains according to Fig. 15, Fig. 16, Fig. 17, Fig. 18 and Fig. 19.


6.5.1. P-N

mode

6.

Press the GO/STOP key on the instrument or the START key on remote
probe. The instrument will start the measurement.

CAUTION

If message “Measuring…” appears on the display, the instrument is
performing measurement. During this whole stage, do not disconnect the
test leads of the instrument from the mains.

7. Once test is completed, if the

measured impedance value
is lower than the full scale,
the instrument gives a
double acoustic signal and
then displays a screen
similar to the one reported
here to the side

L O O P

1.07

2 1 5 A

FRQ=50.0Hz
VP-N=228V

VP-Pe=228V

Measured impedance value

Prospective short circuit current

P-N and P-PE measured voltages

P-N STD

Func

Mod.

Advertising