6.6. R

A

15MA:

MEASUREMENT OF THE TOTAL EARTH RESISTANCE THROUGH
THE SOCKET-OUTLET

This function is performed in compliance with standards IEC/EN61557-6 and allows
measuring the impedance of the fault loop, comparable to the overall earth resistance in
TT systems. One single operating mode is available.

CAUTION

The measurement of the overall earth resistance involves the circulation of a
current between phase and earth according to the technical specifications of
the instrument (§ 12.1). This could cause the tripping of possible protections
at lower tripping currents.

Fig. 20: Instrument connection for 230V single-phase or double-phase P-PE fault loop

impedance measurement through shuko cable

Fig. 21: Instrument connection for 230V single-phase or double-phase P-PE fault loop

impedance measurement through single cables and remote probe

Fig. 22: Instrument connection for 400V + N + PE three-phase P-PE fault loop impedance

measurement through single cables and remote probe

Fig. 23: Instrument connection for 400V + PE (no N) three-phase P-PE fault loop

impedance measurement through single cables and remote probe