HT instruments SPEED418 User Manual

Page 27

Advertising
background image

400

Series

EN - 26

Fig. 12: Instrument connection for 400V + N + PE three-phase RCD test by means of

single cables and remote probe

Fig. 13: Instrument connection for 400V + N (no PE) three-phase RCD test by means of

single cables and remote probe

Fig. 14: Instrument connection for 400V + PE (no N) three-phase RCD test by means of

single cables and remote probe

1.

Press the MENU key, move the cursor to RCD
in the main menu by means of the arrow keys
(,) and confirm with ENTER. Subsequently
the instrument displays a screen similar to the
one reported here to the side.

R C D

---ms

FRQ=50.0Hz

Ut=0.0V

VP-N=230V

VP-Pe=230V

x1 30mA

50V

Func

IdN RCD UL

2.

Use the ,  keys to select the parameter to be modified, and the ,  keys
to modify the parameter value.
It is not necessary to confirm the selection with ENTER

.

Func

The virtual Func key allows setting the measuring mode of the

instrument, which may be: AUTO, x½, x1, x2, x5, , RA

IdN

The virtual IdN key allows setting the nominal value of the RCD’s
tripping current, which may be: 10mA, 30mA, 100mA, 300mA,
500mA, 650mA