400 series, The previous anomalous results cannot be saved – HT instruments SPEED418 User Manual

Page 35

Advertising
background image

400

Series

EN - 34

14. If the instrument detects that, in

case the test should be
performed, a contact voltage
higher than the set limit would
build up in the system being
tested, it does not perform the
test and displays the message
reported here to the side.
Check the efficiency of the
protective conductor and the
earthing

R C D

---ms

FRQ=50.0Hz

Ut=0.0V

VP-N=231V

VP-Pe=231V

Ut > Ulim

The instrument detects a dangerous
contact voltage

x1 30mA

50V

Func

IdN RCD UL

15.

If the RCD trips while
performing the preliminary
checks (automatically
performed by the instrument
before performing the
selected test), the instrument
displays the message
reported here to the side.
Check that all loads
connected downstream of the

R C D

---ms

FRQ=50.0Hz

Ut=0.0V

VP-N=231V

VP-Pe=231V

RCD TRIPPED

RCD tripped during preliminary
checks

x1 30mA

50V

Func

IdN RCD UL

RCD being tested are disconnected and that the set value for IdN matches the RCD
being tested

16. If, after repeated tests, the

instrument has overheated,
the message reported here
to the side is displayed. Wait
for this message to
disappear before performing
other tests

R C D

---ms

FRQ=50.0Hz

Ut=1.4V

VP-N=231V

VP-Pe=231V

Hot temperature

Overheated instrument

x1 30mA

50V

Func

IdN RCD UL

17.

The previous anomalous results cannot be saved