General description – HT instruments SPEED418 User Manual

Page 7

Advertising
background image

400

Series

EN - 6

2. GENERAL DESCRIPTION

2.1. INTRODUCTION
The instrument you purchased, if used in compliance with the instructions given in this manual,
will guarantee accurate and reliable measures. This manual covers following products:
ISO410, SPEED418, COMBI419, COMBI420. The differences in model characteristics are
described in the following table:

Function ISO410

SPEED418

COMBI419

COMBI420

AUTO

LOW

M

RCD

and

Ra 15mA

LOOP

123

AUX

LEAKAGE 

POWER 

Tab. 1: Characteristics of 400 Series models


2.2. INSTRUMENT OPERATION
The instrument can perform following tests (compatibly with the characteristics described
in the table above):

AUTO

Test which automatically performs the following test sequence: total
earth resistance through socket, tripping time of the differential switch,
insulation resistance between phase and earth.

LOW

Continuity test of earth conductors, protective conductors and equipotential
conductors with test current higher than 200mA and open circuit voltage
between 4V and 24V.

M

Insulation resistance measurement with a direct test voltage of 50V, 100V,
250V, 500V or 1000V.

RCD

Measurement of following parameters on A-type (

) and AC-type (

)

general and/or selective differential switches: tripping time, tripping current,
contact voltage (Ut), total earth resistance (RA).

LOOP

Measurement of line impedance and fault loop impedance with
calculation of the assumed fault current.

Ra 15mA

Measurement of total earth resistance with 15mA without causing the
differential protections’ tripping.

123

Indication of the phase sequence.

AUX

Measurement of the environmental parameters (temperature, humidity, air
speed, lighting and noise level) by means of optional probes.

LEAKAGE

Function for measuring leakage current in real time by means of an
(optional) HT96U clamp.

POWER

Real-time displaying the values of the electrical quantities in a single-
phase system and the harmonic analysis of voltage and current up to
the 49

th

harmonic with THD% calculation.