Badger Meter Vortex Meters User Manual

Page 23

Advertising
background image

Page 21

process pressure source - There are four different sources that can be selected for the pro-

cess pressure:

• An absolute pressure analog input

• A gauge pressure analog input

• A user defined pressure value

• The steam table.

NOTE: The analog inputs selections are not available on “non-compensating” models.

Analog Input (Absolute) - This pressure source allows the user to input absolute pressure

information into the meter using the meter’s analog input. This selection requires the user to

connect a 4-20 mA absolute pressure transducer to the terminal block. An absolute pressure

transducer can provide real-time process pressure information. With real-time temperature

information, the meter can compensate for mass flow and standard flow measurements when

the pressure changes. When this pressure source is selected, the user must also enter the

appropriate pressure range information into the “Pressure Reading for 4 mA Analog Input” and

“Pressure Reading for 20 mA Analog Input” fields.

Analog Input (Gauge) - This pressure source allows the user to input gauge pressure infor-

mation into the meter using the meter’s analog input. This selection requires the user to con-

nect a 4-20 mA gauge pressure transducer to the terminal block. A gauge pressure gauge

can provide real-time process pressure information. With real-time temperature information,

the meter can compensate for mass flow and standard flow measurements when the pres-

sure changes. When this pressure source is selected, the user must also enter the appropriate

pressure range information into the “Pressure Reading for 4 mA Analog Input” and “Pressure

Reading for 20 mA Analog Input” fields.

User Defined - The user defined pressure source can be selected to specify a constant pro-

cess pressure. If this pressure source is selected, the pressure value entered in the “User

Defined Pressure” field is used as the process pressure. When the “User Defined” pressure

source is selected, the meter cannot compensate for mass flow or standard flow measure-

ments when the pressure changes.

steam Table - The “Steam Table” pressure source can only be selected on steam meters.

When this pressure source is selected, the meter uses the process temperature and a saturat-

ed steam table to determine the process pressure. This function assumes saturated steam and

will not accurately calculate the pressure of superheated steam.

NOTE: The steam table cannot be selected as the “Process Pressure Source” if the “Steam Table” has already

been selected as the “Process Temperature Source” in the “Process Temperature” dialog box.

See the process temperature section of this manual for typical scenarios for selecting tempera-

ture and pressure sources.