Badger Meter Vortex Meters User Manual

Page 34

Advertising
background image

Totalizer enabled - The totalizer is running when this box is checked. The totalizer can also

be started and stopped by checking and un-checking this box. However, the totalizer value is

set to zero whenever the totalizer is configured using the “Totalizer Settings” dialog box. For

normal operation, use the controls provided by the totalizer dialog box under the “Tools” menu

to start, stop, and reset the totalizer.

Totalizer Multiplier - The totalizer can be configured with a multiplier in the range of 1

-12

to

1

12

. The accumulator is adjusted by the “Multiplier” value before it is displayed. For example, if

the total is 5000 lbs and the multiplier is 0.001, the totalizer value displayed on the LCD or via

HART is 5.

Totalizer Rollover - The rollover value of the totalizer can be configured from 1 to 1

27

. The to-

talizer will rollover to zero when it reaches the rollover value. If the rollover value is set to 100,

the totalizer will count to 100, reset to zero, and then begin counting up again.

Custom unit - This field allows the user to enter a custom totalizer unit. The “Custom Unit” is a

text string and can be up to eight characters long. The default “Custom Unit” is all blanks. This

value is only displayed as the totalizer unit when the “Multiplier” is not 1.0.

NOTE: Save the changes to EEPROM and put the meter in-service after making changes.