2 Assembly and installation

BU 0290 GB-4312

Subject to technical amendments

15

2.2.2

Control connections

2.2.2.1 Field bus (PROFINET IO)

Specification

PROFINET IO

Max. baud rate 100 MBaud

Electrical isolation 500V

eff

Bus connection

2

RJ45

Bus termination

Performed automatically by the SK TU4-

… technology unit

Cable

Ethernet CAT-5 or better

Max. cable length

100m between two Ethernet bus modules

Supply voltage

24V

20%, current consumption

≈ 100mA

Reverse polarity protected

Status display

4 LEDs

Device address

via the PROFINET IO controller or parameterisation

PE

Connection via plug pins under the 24V supply

Shield

The shields of the two RJ sockets are connected together and connected to PE with a
high resistance and capacitance.

Table 2 Electrical specifications of the SK TU4-PNT


The field bus cable must only be connected to the two RJ45 sockets mounted on the front.

Signal

Name

RJ45 Pin

TX+

Transmission Data +

1

TX-

Transmission Data -

2

RX+

Receive Data +

3

RX-

Receive Data -

6

Table 3 RJ45 socket connections

2.2.2.2 Peripherals (system bus and IOs)

The PROFINET IO modules must be provided with a 24V DC (±20%, 100mA) control voltage. Wire end
sleeves must be used for flexible cables.

Designation

Data

Rigid cable cross-section

0.14 … 2.5mm²

Flexible cable cross-section

0.14 … 1.5mm²

AWG standard

AWG 26-14

Tightening torque (for screw terminals)

0.5 … 0.6Nm


Within the terminal box (unshielded cable section) the data cables (system bus) must be installed as short as
possible and of equal length. Associated data cables (e.g.: Sys+ and Sys-) must be twisted.

Pin 1

Pin 8