background image

5 PROFINET - Data transfer

BU 0290 GB-4312

Subject to technical amendments

33

5.1.4

FI Status Machine

The frequency inverter passes through a status machine. The changes between various states are triggered
by the respective control commands in the process data control word. The actual status is returned in the
process data status word.
After switching on, the inverter is in switch-on disabled status. This status can only be ended by transmitting
the “Shut down (Off 1)” command.
The answer to a master telegram normally does not yet contain a reaction to the control command. The
controller must check the answers from the slaves as to whether the control command has been carried out.

Status

Bit 6

Switch-on

disable

Bit 5

Emergency

stop

Bit 4

Disable

voltage

Bit 3

Fault

Bit 2

Operation

enabled

Bit 1

Standby

Bit 0

Ready for

switch-on

Not ready to start

0

X

X

0

0

0

0

Starting disabled

1

X

X

0

0

0

0

Ready to start

0

1

1

0

0

0

1

Activated

0

1

1

0

0

1

1

Operation enabled

0

1

1

0

1

1

1

Fault

0

X

X

1

0

0

0

Error active

0

X

X

1

1

1

1

Emergency stop active

0

0

1

0

1

1

1

Table 18 Codes for FI status