NORD Drivesystems BU0290 User Manual

Page 57

Advertising
background image

6 Parameters

BU 0290 GB-4312

Subject to technical amendments

57

6.2.3

BUS module information parameters, general (P17x)

Parameters

Setting value / Description / Note

Device

Parameter

type

P170

... [-01]

... [-02]

Present error

(Present fault / error)

SK TU4-PNT

16 bit

0 ... 9999

Actual error present. Further details in Section 7.2 "Error messages".
… [-01 ] = Current module error
… [-02 ] = Last module error

Possible values:

1000 = EEPROM error

1010 = System bus 24V missing

1020 = System bus timeout (see time in P151)

1030 = System bus OFF

Specific to PROFINET IO)

5500 = No Ethernet connection

5501 = Hardware error

P171

... [-01]

...

... [-03]

Software version

(Software version / revision)

SK TU4-PNT

16 bit

0,0 ... 9999.9

This parameter shows the software and revision numbers in the module. Array 03 provides
information about any special versions of the hardware or software A zero stands for the
standard version.
… [-01]
= Software version
… [-02] = Software revision
… [-03] = Special version

P172

Configuration

(Configuration)

SK TU4-PNT

16 bit

0 ... 3

The version can be queried in this parameter.

Possible displayed values:

0 = Internal module (SK CU4)
1 = External module (SK TU4)
2 = Bus TB via SPI (SK TU3)

Advertising