6.2.4

Module information parameters specific to the bus (P18x)


Access:

Read only

Parameters

Setting value / Description / Note

Device

Parameter

type

P180

… [-01]

… [-07]

PPO TYPE

(PPO Type / Module ID)

SK TU4-PNT

8 bit

0 ... 7

The module ID (see gsdml file) for the slots can be queried with this parameter. Caution:
meaningful values can only be read out with an existing AR.

Possible values:

0 = Empty slot

1 = Reserved slot

2 = DIG-IO, Process data for the TU

3 = PPO3, Process data for the FI

4 = PPO4, Process data for the FI

5 = PPO6, Process data for the FI

6 = PPO1, Process or parameter data for the FI

7 = PPO2, Process or parameter data for the FI

[-01] = Reserved

[-02] = Reserved

[-03] = Slot 3 (FI)

[-04] = Reserved

[-05] = Reserved

[-06] = Reserved

[-07] = Reserved

P181

… [-01]

… [-06]

MAC address

(MAC address)

SK TU4-PNT

8 bit

0 ... 255

The Ethernet address (MAC address) can be read out from this parameter.

[-

01] … [-03]

PROFINET identification

[-

04] … [-06]

Manufacturer's address range (NORD: from 03.60.00)


Example:

(00:0E:CF:03:60:00)

P185

… [-01]

… [-04]

Present IP address

(Present IP address)

SK TU4-PNT

8 bit

0 ... 255

The present IP address can be read out from this parameter.
This may deviate from the saved address (P160) if the PROFINET IO controller reconfigures the
parameter.
[-

01] … [-04]

IP address

P186

… [-01]

… [-04]

Present IP sub-net mask

(Present IP sub-net mask)

SK TU4-PNT

8 bit

0 ... 255

The present IP mask can be read out from this parameter.
This may deviate from the saved mask (P161) if the PROFINET IO controller reconfigures the
parameter.
[-

01] … [-04]

IP mask

NOTE

When activated, the functions Disable Current, Quick Stop, Remote Control and
Acknowledge Error, are available at the (local) terminals. To operate the drive, a High
signal must be present on the digital inputs being used before the drive can be enabled.