1 general, 1 the bus system – NORD Drivesystems BU0290 User Manual

Page 6

Advertising
background image

PROFINET bus module for NORD frequency inverters SK 200E

6

Subject to technical amendments

BU 0290 GB-4312

1 General

Modern field bus systems, microcontrollers and communication networks have had a great influence on
automation systems and have resulted in greater flexibility, availability and ultimately, also a reduction in
costs.
The widespread use of PC-based control only became possible with the availability of field bus systems.
With increasing control unit performance, the classic field bus ultimately became the limiting criterion for the
entire system. It was therefore an obvious step to adapt Ethernet technology, which provides high rates of
data transmission in IT applications, to the field of automation.

1.1 The bus system

As a physical transfer medium, PROFINET® transfers many years of experience with PROFIBUS-DP-V1 to
Fast Ethernet. In addition to the conventional open Ethernet communication TCP/IP it enables real time
communication of process data. PROFINET defines three communication classes, which provide different
levels of efficiency and functionality:

TCP/IP or UDP/IP communication without real time capability

Real time communication for process data (>1ms) RT

Isochronous real time communication for synchronised process data  IRT


Features of the SK TU4-PNT(-C)

PROFINET IO real time communication (RT=Real Time and IRT=Isochronous Real Time)

Automatic address assignment via the IO controller using DCP (discovery configuration protocol)

Switched Ethernet

Autonegotiation (negotiation of transfer parameters)

Autocrossover (Transmission and reception cables crossed over in the switch)

Conforms with Class B, C

PROFINET IO bus cable connection via RJ45 plug - connector

Connection of I/Os and system bus via screw terminals and optionally via M12 round connectors

Display of specific PROFINET IO status with 2 LEDs

Specific DEVICE or FI status display with 2 LEDs

Eight integrated 24V inputs and two 24V outputs

Available as a version in a separate housing (optionally IP55 / IP66)

An interface (RS232/RS485) via an integrated RJ12 socket is available for parameter access by

means of the manual control unit SK PAR-3H or via NORDCON software.

Performance

Electrically isolated bus interface 500V

eff

100Mbit/s data communication

Full duplex transmission

Transmission of a maximum of five setpoints or actual values to the frequency inverter

Cyclic parameterisation (PPO 1 + 2) or acyclic parameterisation (Records)

PROFINET Bus Gateway solution

→ up to 4 frequency inverters can be connected to a PROFINET

bus module

Almost unlimited participants in the PROFINET system possible (limited by the controller)