5 PROFINET - Data transfer

BU 0290 GB-4312

Subject to technical amendments

31

5.1.2

Control word

The control word (STW) is the first word transferred to the frequency inverter in the process data area in an
order telegram. For example, a control word "Ready for switch-on" corresponds to 047E

(hex)

. In general the

command "Standby" should be the first command which is transferred to the inverter.

Bit Value Meaning

Remarks

0

0

Not ready for operation

Reverse with the brake ramp, with disconnection from supply at f=0Hz (OFF1)

1

Ready for operation

Frequency inverter ready for operation

1

0

Disable voltage

Cut off voltage; the inverter output voltage is switched off; the FI enters a state
where switching on is disabled. (OFF2)

1

Do not disable voltage

Operating condition OFF 2 is cancelled

2

0

Emergency Stop active

Quick stop with programmed quick stop time; with disconnection from supply
at f=0Hz; the FI switches to starting disabled condition (OFF3).

1

Emergency Stop not active

Operating condition OFF 3 is cancelled

3

0

Disable operation

Disable voltage; the inverter output voltage is switched off; the FI enters a
state where switching on is enabled.

1

Enable operation

The output voltage is enabled; ramp to the existing setpoint

4

0

Pulse not enabled

Ramp generator is set to zero; no disconnection from supply at f=0Hz; FI
remains in the operation enabled state.

1

Enable pulses

Ramp generator enabled

5

0

Ramp not enabled

The setpoint currently provided by the ramp generator is "frozen" (frequency is
maintained).

1

Enable ramp

Setpoint on ramp generator enabled.

6

0

Setpoint not enabled

Selected setpoint value is set to zero on the ramp generator.

1

Enable setpoint

Selected ramp generator setpoint is activated.

7

0

No acknowledgement

With the switch from 0 to 1, errors which are no longer active are
acknowledged.

1

Acknowledge error (01)

Note: If a digital input has been programmed for the "ack.fault" function, this
bit must not permanently be set to 1 via the bus (otherwise, flank evaluation
would be prevented).

8

0

1

Start function 480, 11

Bus bit 8 from the control word is set. Only for SK 2xxE and SK 5xxE. For
further details of the function please refer to parameter (P480).

9

0

1

Start function 480, 12

Bus bit 9 from the control word is set. Only for SK 2xxE and SK 5xxE. For
further details of the function please refer to parameter (P480).

10

0

Control data invalid

The transmitted process data is invalid.

1

Control data valid

Valid process data is transferred from the master.
Note: In order for the transmitted setpoint to be valid, this bit must also be set
(setting: interface), even if only setpoint values are transmitted via the bus.

11

0

1

Rotation right is on

Rotational direction right (priority) ON*

12

0

1

Rotation left is on

Rotational direction left ON*

13

0/1

Reserved

Reserved

14

0/1

Parameter set Bit 0 ON

00 = Parameter set 1
01 = Parameter set 2

10 = Parameter set 3
11 = Parameter set 4

15

0/1

Parameter set Bit 1 ON

* If Bit 12=0, then "Direction of rotation right ON" applies

Table 16 Meaning of individual control word bits