PROFINET bus module for NORD frequency inverters SK 200E

64

Subject to technical amendments

BU 0290 GB-4312

7.2.2

Table of possible error messages in the bus module

The following error messages concern bus-related messages, which are indicated on the PROFINET module
SK TU4-PNT(-

…)) All SK TU4-PNT error messages are displayed in parameter (P170) of the bus module and

trigger an error in the connected FI. This is permanently stored in the FI error statistics. The error messages in
the bus module memory (P170) parameter are lost when the 24V supply voltage is switched off.

Error number

Fault

Text in the ParameterBox

Cause

Remedy

Group

Details in
P170

E1000

1000

EEPROM error

Module faulty

1010

System bus 24V missing

Check connections and supply cables

Ensure 24V voltage supply

1020

System bus timeout

Check time set in parameter (P151).

Telegram transfer is faulty.

Check external connection

Check bus protocol program process.

Check bus master.

1030

System bus OFF

Check connections and supply cables

Ensure 24V voltage supply

Check bus master.

5500

No Ethernet

No Ethernet connection

Connect module to Ethernet

5501

Hardware error, IO chip

EMC fault or IO chip defective

Check connections, shielding, cable run

Restart module