2 parameter settings of the frequency inverter – NORD Drivesystems BU0290 User Manual

Page 26

Advertising
background image

PROFINET bus module for NORD frequency inverters SK 200E

26

Subject to technical amendments

BU 0290 GB-4312

4.2 Parameter settings of the frequency inverter

4.2.1

Parameter settings of the SK 200E frequency inverter

The following settings must be made on the SK 200E:

FI address (preferably set via DIP switches (DIP1 and 2)), if several FIs are connected to an
SK TU4-PNT (Gateway mode)

Set the control and setpoints (preferably via DIP switches (DIP3)), or via parameter:

Control via "system bus"  P509 = 3

Setpoints via "system bus"  P510 = 3 or 0 if P509 = 3

Setting of setpoints via P546 [-

01] … [-03]

Setting of actual values via P543 [-

01] … [-03]

A precise description of the parameters can be found in Section 6.1 of this supplementary manual or in the
SK 200E operating manual.
The parameters can be set with NORD parameterisation tools or via the PROFINET IO controller.

4.2.2

Parameter settings of the SK 500E frequency inverter

The following settings must be made on the SK 500E:

Control via "CANopen"  P509 = 6

Setpoints via "CANopen"  P510 = 6 or 0 if P509 = 6

Setting of setpoints via P546, P547 and P548 (SK 54xE and above: P546 [-

01] … P546 [-05])

Setting of actual values via P543, P544 and P545 (SK 54xE and above: P543 [-

01] … P543 [-05])

Setting of system bus monitoring via P513 = 0.6s

Setting of the baud rate via P514 = 5 (corresponds to 250kB)

Setting of the system bus addresses via P515 [-01] = 32, 34, 36 or 38

For a detailed description of the parameters, please refer to the SK 500E operating manual.
The parameters can be set with NORD parameterisation tools or via the PROFINET IO controller.