NORD Drivesystems BU0290 User Manual

Page 22

Advertising
background image

PROFINET bus module for NORD frequency inverters SK 200E

22

Subject to technical amendments

BU 0290 GB-4312

3.1.2.2 PROFINET displays

The communication status of the PROFINET IO module is indicated by the LEDs RUN and BF.

RUN = PROFINET IO bus status
BF = PROFINET IO bus fault

PROFINET IO status display

RUN

Green LED

Meaning

Flashing = 2.5 Hz (0.4 s cycle  0.2 s on / 0.2 s off)

OFF

Module not in operation

Device switched off or initialisation

Flashing

Waiting for AR (no connection to the PROFINET-IO controller)
 no parameter communication
 no process data communication

ON

AR established (a connection to the PROFINET IO controller has been set up)
 Parameter communication active
 Process data communication active

Table 6 RUN LED display

PROFINET IO error display

BF

Red LED

Meaning

Flashing = 2.5 Hz (0.4 s cycle  0.2 s on / 0.2 s off)

Double flash = 2 x brief flashes

OFF

No error

Flashing

Incorrect configuration
General PROFINET configuration error,
can be caused by a false GSDML file.

ON

Ethernet error
 SK TU4-PNT is not (physically) connected to an Ethernet participant

Double Flash

Watchdog - Timeout
 PROFINET or FI timeout (P151)

Table 7 BF LED display


The physical status of the field bus system (PROFINET IO) is indicated by the LINK /ACTIVITY LEDs, which
are located directly next to the RJ45 socket on the front panel.

Display of PROFINET Link and Active connections

Link

Green LED

Activity

Yellow LED

Meaning

Off

Off

Port (RJ45 socket) is not connected to the PROFINET network

On

Off

Port (RJ45 socket is connected to the PROFINET network, but there
is no exchange of data

On

On / Flashing

Data exchange via PROFINET active

Table 8 LED display, Link and Activity