PROFINET bus module for NORD frequency inverters SK 200E

52

Subject to technical amendments

BU 0290 GB-4312

Parameters

{Factory setting}

Setting value / Description / Note

Device

Supervisor

Parameter

set

P552

… [-01]

… [-02]

CAN master cycle

(CAN master cycle time (system bus))

SK 2xxE

S

0 / 0.1 … 100.0 ms
{ 0 }

In this parameter, the cycle time for the system bus master mode and the CAN open encoder is
set (see P503/514/515):
… [01] = Cycle time for system bus master functions
… [02] = Cycle time for system absolute value encoder

With the setting 0 = "Auto" the default value (see table) is used.

According to the Baud rate set, there are different minimum values for the actual cycle time:

Baud rate

Minimum value t

Z

Default system bus master

Default system bus abs.

10kBaud

10ms

50ms

20ms

20kBaud

10ms

25ms

20ms

50kBaud

5ms

10ms

10ms

100kBaud

2ms

5ms

5ms

125kBaud

2ms

5ms

5ms

250kBaud

1ms

5ms

2ms

500kBaud

1ms

5ms

2ms

1000kBaud:

1ms

5ms

2ms

P560

Parameter, saving mode

(Parameter, saving mode)

SK 2xxE

S

0 ... 1

{ 1 }

0 = Changes to the parameter settings are no longer saved on the EEPROM. Previously

saved settings remain stored, even if the FI is disconnected from the mains; however
new changes are not saved after a mains failure.

1 = All parameter changes are automatically written to the EEPROM and remain stored there

even if the FI is disconnected from the mains supply.

NOTE:

If BUS communication is used to implement parameter changes, it must be
ensured that the maximum number of write cycles (100,000 x) in the EEPROM is
not exceeded.