LASTVAL Command

If the value in the report changes to ////, you can check the
measurement’s/sensor’s value with the LASTVAL command. Give the
command in the terminal connection. When you use the raw parameter,
the measured value before any validation and the status produced
during validation are shown. When you use the corresponding signal
name, the validated value is shown.

LASTVAL [Measurement] [unconv | Signal name]

Examples:

The command with the signal name parameter (in the following case,

TA

) produces the following response:

/ > LASTVAL TAMeasQMH101_1 TA
Status:1 Value:20.490570

where
Measurement

=

Name of the measurement as it is defined in the
setup file

unconv

=

Parameter that gives the status and the electrical
value of the measurement signal before
conversion

Signal name

=

Parameter that gives the validated value of the
measurement

where
Status:1

=

Value is valid.

Value:20.490570

=

Validated value for the temperature
measurement is 20.49xxxx.