Table 4, Analog measurement channels, Table 5 – Vaisala Hydromet Data Collection Platform User Manual

Page 25: Power channels

Advertising
background image

Chapter 2 __________________________________________________________ Product Overview

VAISALA_______________________________________________________________________ 23

3.

One connector block for communication channels.

4.

Two blocks for optional communication modules.

Single-ended (H-C or L-C) or differential (H-L) measurements can be
performed in the 10 measurement channels.

NOTE

Each sensor in a basic setup has its own dedicated channel.

Table 4 on

page 23

is to be used for reference purposes only.

Table 4

Analog Measurement Channels

Channels

Pin Name Description

CH0, CH1, CH2,
CH3 24-bit ADC

E

12 V/25 mA voltage excitation ON/OFF,
voltage can be measured.
OR: 100

A/1mA current excitation.

H

Analog input (High)

L

Analog input (Low)

C

The pin has been connected to ground
(GND) via a 10

 resistor so that the

current can be measured.

CH4, CH5, CH6,
CH7 24-bit ADC

E 100

A/1 mA current excitation

H Analog

input

(High)

L Analog

input

(Low)

C

Common return and reference level for
voltage measurements via the channel's
own E-, H-, and L-pins. The pin has been
connected directly to ground.

CHA, CHB Suitable
for fast-changing
input signals 12-bit
ADC

F

Frequency input

E

0 ... 12 V/20 mA adjustable excitation
voltage, can be measured.

H

Fast analog input (High)

L

Fast analog input (Low)

C

Common return (Analog ground)

Table 5

Power Channels

Pin Name

Description

GND

Ground

SDI-12

SDI-12

GND

Ground

+ExtDC

8 ... 30 VDC