Set voltage for led alarm, Extend analog output range – Vaisala MMT162 User Manual

Page 38

Advertising
background image

User's Guide ______________________________________________________________________

36 __________________________________________________________________ M210934EN-C

Hysteresis : 0.50

Level Lo : 0.20

Level Hi : 0.80

Channel 2:

Low Limit : OFF

High Limit : ON

Aerr : OFF

Quantity : aw

Limit Lo : 0.10

Limit Hi : 0.90

Hysteresis : 0.01

Level Lo : 0.20

Level Hi : 0.80

Set Voltage for LED Alarm

With the LED command, you can set a different voltage level for each

channel.

LED<cr>

Example:

led ?

Ch 1 Led Voltage : 2.80 V

Ch 2 Led Voltage : 2.80 V

Extend Analog Output Range

Use the AOVER command to allow the analog output channels to

exceed their specified range by 10 %. The scaling of the parameter

remains as before; the extra range is used for additional measurement

range in the wet end.

AOVER [ON/OFF]<cr>

Example:

aover on

: ON