Red Lion GEMINI 2 User Manual

Page 12

Advertising
background image

CODE 51 - RESET MODES (Cont’d)

[51 3] AUTOMATIC RESET TO ZERO AFTER OUTPUT TIME DELAY -

The counter resets to zero when the output time delay ends. Manual reset

is “maintained” and will override automatic reset.

[51 4] AUTOMATIC RESET TO PRESET AFTER OUTPUT TIME DELAY -

The counter resets to the preset value when the output time delay ends.

Manual reset is “maintained” and will override automatic reset.

[51 5] AUTOMATIC RESET TO ZERO AT THE BEGINNING OF THE

OUTPUT TIME DELAY - When in this reset mode, the unit will

automatically reset to zero at the beginning of the output time delay (when

the preset point is reached). For the Gemini 2000, the output 1 and output 2

time delays must be shorter than the time required for the counter to count

to the preset 2 value. Otherwise, the output(s) will appear to be latched on.

Manual reset is “maintained” and will override automatic reset.

[51 6] AUTOMATIC RESET TO PRESET AT THE BEGINNING OF THE

OUTPUT TIME DELAY - In this reset mode, the unit will automatically

reset to preset at the beginning of the output time delay (when zero is

reached). For the Gemini 2000, the output 1 and output 2 time delay must

be shorter than the time required for the counter to count to zero.

Otherwise, the outputs will appear to be latched on. Manual reset is

“maintained” and will override automatic reset.

[51 -1]

[51 -2]

[51 -3]

These modes are the same as above with the exception

[51 -4]

that Reset is set for “momentary” operation.

[51 -5]

[51 -6]

CODE 52 - OUTPUT 1 TERMINATION MODES

The Gemini has six Output Termination Modes. They are: Terminate at

Output 2 Start; Terminate at Output 2 End; Terminate at Manual Reset;

Terminate at Manual Reset End; Terminate After Time Delay; and Boundary.

A Reverse Phase Option is available on the Gemini. This refers to

complementing the logic state of the output. With normal phase operation, when

the count reaches preset 1 the output will turn on. The reset condition of the

output is output off. In reverse phase operation, the output turns off when the

preset is reached. The reset condition of the output is output on. (Note: The state

of the relay, if used, is also reversed.) A “-” sign in front of the mode identifier

will provide for reverse phase operation. The absence of a “-” sign will give

normal phase operation.

In all modes except boundary, when the unit is powered up, the relays or

outputs will be turned off. This is done to help prevent a hazardous situation from

occurring. If other than boundary or time delay operation is selected, the unit

should be reset upon power up.
[52 1] TERMINATE AT OUTPUT 2 START - Output 1 will terminate when

Output 2 starts. (Gemini 2000 only)

[52 2] TERMINATE AT OUTPUT 2 END - Output 1 will terminate when

Output 2 terminates. (Gemini 2000 only)

[52 3] TERMINATE AT MANUAL RESET - In this mode, output 1, once

activated, does not deactivate until the moment a reset occurs. The reset can be

from the front panel button or from the remote reset terminal at the rear of the

unit. The output is set for normal phase operation.

[52 4] TERMINATE AT MANUAL RESET END - This mode is like the

preceding output mode, except output 1 deactivates when the reset ends. The

output is set for normal phase operation.

[52 5] TERMINATE AFTER OUTPUT 1 TIME DELAY - Once output 1 has

been activated, it will deactivate after the predetermined length of output 1

time delay has expired. Manual reset, by either the front panel button or the

reset terminal, will override the output 1 time delay and reset the output. The

output is set for normal phase operation.

[52 6] BOUNDARY MODE - This mode can be used when the unit is

functioning as a counter, but is more applicable to the rate indicator mode.

When in boundary mode, the preset 1 value serves as the boundary point.

When the count is less than the preset, the output is not activated (normal

phase). When the count is greater than or equal to the preset, the output is

activated. If the count value were to drop below preset, the output would again

deactivate. For negative preset points, the output is not activated when the

count value is more positive than the preset value. When the count is more

negative than or equal to the preset, the output is activated. If the count

becomes more positive than the preset, the output again deactivates. Upon

power up, the output will “remember” its power down boundary condition

and go to that state. The output is set for normal phase operation.

–10–

Advertising
This manual is related to the following products: