CURRENT LOOP INSTALLATION

WIRING CONNECTIONS

When wiring the 20 mA current loop, remove the 7-position terminal block

(TBD), located on the right side of the top board. Refer to the numbers listed with

the terminal descriptions below or on the top label, and install each wire in its

proper location on the terminal block. When all connections are made, replace

the terminal block into its proper location.

It is recommended that shielded (screened) cable be used for serial

communications. This unit meets the EMC specifications using Alpha #2404

cable or equivalent. There are higher grades of shielded cable, such as, four

conductor twisted pair, that offer an even higher degree of noise immunity.
TERMINAL DESCRIPTIONS FOR TERMINAL BLOCK TBD

1. -20 mA SRC (COMMON) - Common for 20 mA SRC & Print Request

terminal.

2. PRINT REQUEST - The Print Request Terminal is connected to common to

request the Gemini 2000 to transmit according to the Print Options mode that

has been selected. (Minimum Activation time = 25 msec.)

3. +20 mA SRC - The 20 mA SRC terminal provides the source current for one of

the loops.

4. SO- (Serial Out-)

5. SO+ (Serial Out+)

The Gemini 2000 transmits the requested data on these terminals (SO- &

SO+). They are connected in series to the receive input of the device to be

connected.

6. SI- (Serial In-)

7. SI+ (Serial In+)

The Gemini 2000 receives commands on these terminals (SI- & SI+). They are

connected in series with the transmit or output terminals of the device to be

connected.

Note: The serial input terminals must be held in the mark condition

(current on) in order for the Gemini 2000 to respond to a Print Request

terminal activation.