Red Lion GEMINI 2 User Manual

Page 30

Advertising
background image

TROUBLESHOOTING GEMINI SERIAL COMMUNICATIONS

If problems are encountered when trying to get the Gemini(s) and host device or

printertocommunicate,thefollowingchecklistcanbeusedtohelpfindthesolution.

1. Check all wiring. Refer to the previous application examples and use them as a

guide to check your serial communication wiring. Proper polarity of all

Geminis and other peripherals must be observed. If a multimeter or ammeter is

available, insert it in series in each Serial loop and check for current flow with

all units powered up. If no current is flowing, either the loop is not wired

correctly, or some other fault has occurred. If too much current has been sent

through a Serial Input or Output, the unit may have been damaged. If a Gemini

is suspected, it can be tested for operation by using the Serial Loop-back test

described in the next section.

2. If the Gemini is set-up with a “host computer”, device or printer, check to make

sure that the computer or device is configured with the same communication

format as the Gemini. The only communication format the Gemini will accept

is; 1 start bit, 7 data bits, odd parity, and 1 stop bit.

3. Check the baud rate settings and make sure all devices in the loop are set to the

same baud rate.

4. Check the Gemini’s unit address. If the Address command is not used when

transmitting a command to the Gemini, the Gemini’s address must be set to 0. See

“Sending Commands & Data to the Gemini” section for command structure.

5. If two-way communications are to be established between the Gemini and a

computer, try getting the computer to receive transmissions from the Gemini

first. The Gemini’s “PRINT REQ.” terminal can be used to initiate the

transmissions from the Gemini.

6. When sending commands to the Gemini, the * (2Ah) must terminate the

command. NO CARRIAGE RETURNS (0Dh) OR LINE FEED (0Ah)

CHARACTERS SHOULD BE SENT TO THE GEMINI. If they are sent, the

Gemini will not respond to the next command.

7. For applications where 1200 Baud or lower is used, the command terminator (*)

can be sent before the string to eliminate any illegally transmitted characters.

SERIAL LOOP-BACK SELF-TEST

The Gemini 2000 has a Serial Loop-back Self-test feature. This test enables the

user to verify the operation of the Gemini when problems are encountered trying to

get the Gemini and “Host device” communicating. In this test, the Gemini’s Serial

Input and Output Loops are connected together with the 20 mA source supplying

the loop current. The Gemini then transmits data “to itself”. If the data is received

properly, the Gemini 2000 will change its Scale Factor value to 0.1111. To perform

the loop-back test, follow the test sequence as described below.

1. With the unit powered down, wire up the serial terminal block, “TBD”, as

shown in the diagram below.

2. Set the Gemini’s unit address to 15 (set switches 7-10 of the Serial DIP Switch

to the down position).

3. Apply power to the unit. On power-up the Gemini will perform the loop-back

test. To check the results: Call up the Scale Factor value by pressing the “3”

key. If the Serial loop is functioning properly the Scale Factor value will be

0.1111. If this result is not obtained, double check the connections with those

shown in the diagram, and the unit address switch positions and repeat step 3.

4. If the connection between the Print Request terminal, “PRINT REQ.” and

“COMMON” is disconnected while the unit is under power, the Scale Factor

value will change back to its previous setting.

If the unit does not pass this test, contact your local Red Lion Controls

distributor.

–28–

Advertising
This manual is related to the following products: