9. SERIAL COMMUNICATIONS (Optional): (Cont’d)

Serial Hardware Specifications -

SO - Output Transistor Rating: V

MAX

= 30 VDC, V

SAT

= 1 V

MAX

at 20 mA.

(Can address 16 units in a loop)

SI - Input Diode Rating: V

F

= 1.25 V

TYP

; 1.5 V

MAX

Note: The compliance voltage rating of the source must be greater than the

sum of the voltage drops around the loop.

10. OUTPUT(S):

Solid-State - Current sinking NPN open collector transistor(s). I

SNK

= 100 mA

maximum. V

OH

= 30 VDC maximum (Internal Zener diode protected). V

OL

=

1 VDC max. @ 100 mA.

Relay(s) - Mounted on a field replaceable P.C. board. Form C contacts rated at

5 amps @ 120/240 VAC or 28 VDC (resistive load), 1/8 H.P. @ 120 VAC

(inductive load). The operate time is 5 msec. nominal and the release time is 3

msec. nominal.

Relay Life Expectancy - 100,000 cycles at Max. Rating. (As load level

decreases, life expectancy increases.)

Programmable Timed Outputs - The timed outputs can be set from 0.01 to

599.99 seconds, ±(0.01% + 10 msec).

11. CERTIFICATIONS AND COMPLIANCES:

SAFETY

IEC 1010-1, EN 61010-1: Safety requirements for electrical equipment

for measurement, control, and laboratory use, Part 1.

IP65 Enclosure rating (Face only), IEC 529

Type 4 Enclosure rating (Face only), UL50

ELECTROMAGNETIC COMPATIBILITY:

Immunity to EN 50082-2

Electrostatic discharge

EN 61000-4-2 Level 2; 4 Kv contact

1

Level 3; 8 Kv air

Electromagnetic RF fields

EN 61000-4-3 Level 3; 10 V/m

80 MHz - 1 GHz

Fast transients (burst)

EN 61000-4-4 Level 4; 2 Kv I/O

Level 3; 2 Kv power

2

RF conducted interference

EN 61000-4-6 Level 3; 10 V/rms

150 KHz - 80 MHz

Power frequency magnetic fields EN 61000-4-8 Level 4; 30 A/m

Emissions to EN 50081-2

RF interference

EN 55011

Enclosure class A

Power mains class A

Notes:

1. Metal bezel of unit connected with ground from rear bezel screw to metal

mounting panel.

2. When the unit is DC powered, a power line filter (RLC# LFIL0000 or

equivalent) was installed, so as not to impair the function of the unit.

Refer to the EMC Compliance Installation section of the manual for

additional information.

12. ENVIRONMENTAL CONDITIONS:

Operating Temperature: 0 to 50°C

Storage Temperature: -40 to 80°C

Operating and Storage Humidity: 85% max. relative humidity

(non-condensing) from 0°C to 50°C.

Altitude: Up to 2000 meters

13. CONSTRUCTION: Metal die-cast bezel, plastic case. This unit is rated

for NEMA 4/IP65 indoor use. Installation Category II, Pollution

Degree 2.

14. WEIGHT: 2.1 lbs (0.9 kg)

–41–

Advertising
This manual is related to the following products: