These modes are the same as above with the exception

[52 -4]

that the output is set for reverse phase operation.

[52 -5]

[52 -6]

CODE 53 - OUTPUT 1 TIME DELAY

The Gemini has the capability of varying the output time delay from 0.01 second

to 599.99 seconds. When the code is entered, instead of a single mode identifier

digit being displayed, six digits will be shown. Refer to the “Programming Preset,

Scale Factor, and Output Time Delay” section for more details about entering.

Output time delay will be terminated if the unit is manually reset.

Note: A time delay value of zero cannot be programmed into the Gemini. If a

value of 0 is entered into the display and the “E” key is pressed, the unit will not

enter the 0, but will revert back to displaying the previous time delay.

CODE 54 - OUTPUT 2 TERMINATION MODES (GEMINI 2000

Only)

The Gemini 2000 has six Output 2 Termination Modes. They are: Terminate at

Output 1 Start; Terminate at Output 1 End; Terminate at Manual Reset;

Terminate at Manual Reset End; Terminate After Time Delay; and Boundary.

A Reverse Phase Option is available on the Gemini 2000. This refers to

complementing the logic state of the output. With normal phase operation, when the

count reaches preset 2, output 2 will turn on. The reset condition of the output is

output off. In reverse phase operation, the output turns off when the preset is reached.

The reset condition of the output is output on. (Note: The state of the relay, if used, is

also reversed.) A “-” sign in front of the mode identifier will provide for reverse

phase operation. The absence of a “-” sign will give normal phase operation.

In all modes except boundary, when the unit is powered up, the relays or

outputs will be turned off. This is done to help prevent a hazardous situation from

occurring. If other than boundary or time delay operation is selected, the unit

should be reset upon power up.

[54 1] TERMINATE AT OUTPUT 1 START - Output 2 will terminate when

Output 1 starts.

[54 2] TERMINATE AT OUTPUT 1 END - Output 2 will terminate when

Output 1 terminates.

[54 3] TERMINATE AT MANUAL RESET - In this mode, output 2, once

activated, does not deactivate until the moment a reset occurs. The reset can be

from the front panel button or from the remote reset terminal, at the rear of the

unit. The output is set for normal phase operation.

[54 4] TERMINATE AT MANUAL RESET END - This mode is like the

preceding output mode, except output 2 deactivates when the reset ends. The

output is set for normal phase operation.

[54 5] TERMINATE AFTER OUTPUT 2 TIME DELAY - Once output 2 has

been activated, it will deactivate after the predetermined length of output 2

time delay has expired. Manual reset, by either the front panel button or the

reset terminal, will override the output 2 time delay and reset the output. The

output is set for normal phase operation.

[54 6] BOUNDARY MODE - This mode can be used when the unit is

functioning as a counter, but is more applicable to the rate indicator mode.

When in boundary mode, the preset 2 value serves as the boundary point.

When the count is less than the preset, the output is not activated (normal

phase). When the count is greater than or equal to the preset, the output is

activated. If the count value were to drop below preset, the output would again

deactivate. For negative preset points, the output is not activated when the

count value is more positive than the preset value. When the count is more

negative than or equal to the preset, the output is activated. If the count

becomes more positive than the preset, the output again deactivates. Upon

power up, the output will “remember” its power down boundary condition

and go to that state. The output is set for normal phase operation.

[54 -1]

[54 -2]

[54 -3]

These modes are the same as above with the exception

[54 -4]

that the output is set for reverse phase operation.

[54 -5]

[54 -6]

–11–