APPENDIX “C” - TROUBLESHOOTING GUIDE (Cont’d)

–44–

PROBLEM

POSSIBLE CAUSE

REMEDIES

CANNOT PROGRAM CODE 52 - 1 , 2

1. 54 -6 is programmed.

1. Change 54 then program 52.

2. Unit is in tachometer mode.

CANNOT PROGRAM CODE 52 - 6

1. 54 - 1, 2 is programmed.

1. Change 54 then program 52.

2. Unit is in tachometer mode.

CANNOT PROGRAM CODE 54 - 1, 2

1. 52 -6 is programmed.

1. Change 52 then program 54.

2. Unit is in tachometer mode.

CANNOT PROGRAM CODE 54 - 6

1. 52 -1, 2 is programmed.

1. Change 52 then program 54.

2. Unit is in tachometer mode.

CANNOT PROGRAM CODE 63

(Sample Time)

1. Unit is in Counter mode.

1. Check function Code 41.

OUTPUT DOES NOT TERMINATE AT

MANUAL RESET END

1. Reset mode set for “Momentary” reset.

1. Change reset mode to “Maintained” reset (51).

Note: For Serial Communication problems refer to “Troubleshooting Gemini Serial Communications” section.